SES-D-101 — Medium-Voltage Cable Joints
Revision 4 · Effective 2025-08-01 · Domain: Distribution
1. Scope
This standard specifies design, material, performance, testing, and installation requirements for medium-voltage cable joints rated 6kV through 36kV used in Saudi Energy distribution networks.
2. Normative references
- IEC 60502-2 — Power cables with extruded insulation
- IEC 61442 — Test methods for accessories
- SES-D-074 — LV Earthing Practices
3. Conductor requirements
Cable joints shall be compatible with both stranded and compacted copper conductors that conform to IEC 60228, Class 2.
3.2.1 Conductor cross-section
Cable joints shall accommodate copper conductors from 25 mm² to 630 mm² per IEC 60502-2, Table 4.
3.2.2 Material
Connector bodies shall be of high-conductivity copper alloy with electroplated tin or nickel finish.
4. Testing
4.1 Partial discharge
Partial discharge testing shall be performed at 1.73 × Uo with a maximum permissible level of 5 pC.
4.3.2 Mechanical pull test
Joints must withstand a longitudinal pull of 30 N/mm² of conductor area for 1 hour without conductor pull-out, splice slippage, or visible deformation.
5. Marking and identification
Each joint shall be permanently marked with manufacturer code, voltage rating, batch number, and date of manufacture in accordance with the SEC marking guideline MG-2024.