SES-D-101 — Medium-Voltage Cable Joints
Owner: N. Al-Harbi · Initiated 2026-02-14 · Last update 2h ago
Workflow
-
InitiationFeb 14
-
Division ReviewFeb 22
-
Committee ReviewIn progress
-
Circulation—
-
Approval—
-
Publication—
Clauses & comments
Open viewer →-
3.2.1Conductor cross-section requirements
Cable joints shall accommodate copper conductors from 25 mm² to 630 mm² per IEC 60502-2, Table 4.
YAY. Al-Mansoori · Committee Chairman · 1h agoRecommend tightening lower bound to 35 mm² to align with current procurement spec.
-
4.1Insulation testing — partial discharge
Partial discharge testing shall be performed at 1.73 × Uo with a maximum permissible level of 5 pC.
-
4.3.2Mechanical pull test
Joints must withstand a longitudinal pull of 30 N/mm² of conductor area for 1 hour.
!Compliance flagTest method does not reference current SEC Test Lab procedure CL-2024-07. Resolve before progression.
-
5.0Marking and identification
Each joint shall be permanently marked with manufacturer code, voltage rating, and date of manufacture.