SES-D-101 — Medium-Voltage Cable Joints

Owner: N. Al-Harbi · Initiated 2026-02-14 · Last update 2h ago

Open viewer

Workflow

  1. Initiation
    Feb 14
  2. Division Review
    Feb 22
  3. Committee Review
    In progress
  4. Circulation
  5. Approval
  6. Publication

Clauses & comments

Open viewer →
  • 3.2.1
    Conductor cross-section requirements

    Cable joints shall accommodate copper conductors from 25 mm² to 630 mm² per IEC 60502-2, Table 4.

    YA
    Y. Al-Mansoori · Committee Chairman · 1h ago

    Recommend tightening lower bound to 35 mm² to align with current procurement spec.

  • 4.1
    Insulation testing — partial discharge

    Partial discharge testing shall be performed at 1.73 × Uo with a maximum permissible level of 5 pC.

  • 4.3.2
    Mechanical pull test

    Joints must withstand a longitudinal pull of 30 N/mm² of conductor area for 1 hour.

    !
    Compliance flag

    Test method does not reference current SEC Test Lab procedure CL-2024-07. Resolve before progression.

  • 5.0
    Marking and identification

    Each joint shall be permanently marked with manufacturer code, voltage rating, and date of manufacture.