Engineer Evaluation Medium risk

WV-2026-0142 — Pull-test alternative for MV cable joints

Affected: SES-D-101 / Clause 4.3.2 · Requested by Al-Yamamah Electric · Due in 2 days

Workflow

  1. Requester
    Apr 19
  2. Proponent
    Apr 21
  3. Division Mgr
    Apr 24
  4. Engineer
    In progress
  5. Dept Mgr
  6. Executive Director

A Request details

Al-Yamamah Electric Co.
SES-D-101 — MV Cable Joints (Rev 4)
4.3.2 — Mechanical pull test
12 months from approval
Replace longitudinal pull test (30 N/mm² × 1h) with combined cyclic-pull procedure per IEC 61442 Annex D, demonstrating equivalent or higher mechanical integrity over 100 cycles.
No impact on installation procedures. Test equipment already deployed at SEC Test Lab — no additional capex required.

B Justification

|

The proposed cyclic-pull procedure has been used internationally since 2018 and is recognized by IEC 61442 Annex D as equivalent or superior for MV joint mechanical qualification. SEC Test Lab has previously evaluated five vendor samples under this method (Reports CL-2024-07, CL-2024-08, CL-2024-09) with conformance correlation of 0.94 to the SES-D-101 procedure.

The cyclic procedure better reflects in-service stress profiles observed in the Eastern Province field surveys (FS-2025-Q1) and would reduce false-fail rates by an estimated 18% based on lab data.

Supporting evidence

SEC Test Lab Reports CL-2024-07 through CL-2024-09 are attached. Field correlation data from Al-Yamamah's installations between 2022–2025 is included in Annex 2.

Previous deviations on this standard

3 found
  • WV-2024-088 — Cable joint dimension tolerance
    Approved · 2024-07-12 · Validity 24mo
    View
  • WV-2023-021 — Alternative crimp connector
    Approved · 2023-03-04 · Validity 12mo (expired)
    View
  • WV-2022-114 — Adhesive material substitution
    Rejected · 2022-09-30
    View